How are control signals transmitted from the FLEX?

The PID analog signal is wired from the FLEX AO connection. Either voltage or mA can be selected.

  1. Select the room and parameter to be controlled
  2. Select Control #
  3. Select Control Preset A or B
  4. Fill in Setpoint, Low Limit, and High Limit (these limits keep it from getting colder or warmer)
  5. Enable

This information is now prepared to provide an analog signal from AO.

To provide the BACnet transfer of this information:

  1. Perform steps 1 through 5 listed above
  2. Select BACnet Setpoint
  3. Fill in Device Inst. (customer provided)
  4. Fill in Object Inst. (customer provided)
  5. Select priority if needed