How are control signals transmitted from the FLEX?
The PID analog signal is wired from the FLEX AO connection. Either voltage or mA can be selected.
- Select the room and parameter to be controlled
- Select Control #
- Select Control Preset A or B
- Fill in Setpoint, Low Limit, and High Limit (these limits keep it from getting colder or warmer)
- Enable
This information is now prepared to provide an analog signal from AO.
To provide the BACnet transfer of this information:
- Perform steps 1 through 5 listed above
- Select BACnet Setpoint
- Fill in Device Inst. (customer provided)
- Fill in Object Inst. (customer provided)
- Select priority if needed