Tell me about the pulse output.

The pulse output is electrically isolated from the meter's power supply and requires the user to connect a voltage source (5-30 VDC), a ground wire (connected to the host ground), and a pull-up resistor. A 10K resistor is the recommended value. The pull up resistor shall be sized to limit the current through the isolator to 5 mA.

Did this answer your question? Thanks for the feedback There was a problem submitting your feedback. Please try again later.