Can 4 to 20 mA input signals be used with Setra Room Monitors?
The 4 to 20 mA signal cannot be inserted directly into the product inputs. The SRCM and FLEX can only accept a voltage input. Using the 4 to 20 mA DC signal with a 250Ω resister will develop a voltage of 1 to 5 VDC. This voltage can be fed directly into the monitor inputs.
The FLEX and SRCM Operating Instructions provide more information:
https://www.setra.com/setra-flex
https://www.setra.com/product/room-pressure-monitoring/model-srcm